Toshiba WX9 ASD Installation & Operation Manual page 196

Table of Contents

Advertisement

Table 10. Discrete Input Terminal Assignment Selections and Descriptions. (Continued)
Sel. No.
NO
NC
66
67
Binary Bit 6 — Used in conjunction with terminal setting 54/55 above.
68
69
Binary Bit 7 — Used in conjunction with terminal setting 54/55 above.
76
77
User Fault 1 — No operation.
78
79
User Fault 2 — No operation.
80
81
User Fault 3 — No operation.
82
83
User Fault 4 — No operation.
86
87
Binary Data Write — This terminal serves two functions:
1) While operating in the Use Binary/BCD input mode, each momentary connection of this terminal to CC transfers the
speed/torque Binary Bit (0 – MSB) settings to the motor.
2) The UP/DOWN frequency command will be saved during power down or reset by setting
terminal to 43:Binary Data Write. If the drive is running and the Binary Data Write terminal is active when an event occurs
(Fault, Power Off), the UP/DOWN frequency command will be restored upon power-up or reset.
88
89
UP/DOWN Frequency (up) — Increases the speed of the motor for the duration of activation until reaching the Upper-Limit
setting or increases the speed of the motor in steps (see
90
91
UP/DOWN Frequency (down) — Decreases the speed of the motor for the duration of activation until reaching the Lower-
Limit setting or decreases the speed of the motor in steps (see
92
93
UP/DOWN Frequency (clear) — Initiates a 0 Hz output command while operating in the UP/DOWN Frequency speed
control mode. If operating with an activated UP/DOWN Frequency (up or down) terminal, the output goes to the Lower-
Limit (F013) setting.
94
95
Push Run — Runs the motor for the duration of the activation at the configured speed and direction.
96
97
Push Stop — Stops the motor for the duration of the activation. Motor resumes normal operation upon deactivation.
98
99
Forward/Reverse Selection — Operates in conjunction with another terminal being set to the Run/Stop (50) function. When
configured to Run (Run/Stop to CC), the make-or-break of this connection to CC changes the direction of the motor.
100
101
Run/Stop Command — Enables the motor to run when activated and disables the motor when deactivated.
102
103
Commercial Power/ASD Switching — Initiates the ASD-to-Commercial Power switching function. See
information on this feature.
104
105
Frequency Command Priority Switching — Connecting this terminal to CC allows for the frequency control to be switched
from the frequency command source selected as Frequency Mode 1 to Frequency Mode 2. This function is enabled by setting
the Frequency Priority Selection to Frequency Source Priority Switching and is located at Program Fundamental
Parameters Standard Mode Selection.
106
107
Terminal Frequency Priority — Overrides the
108
109
Terminal Command Priority — Overrides the
110
111
Parameter Edit Enable — Allows for the override of the lock out parameter setting allowing for parameter editing.
112
113
Control Switching (speed/torque) — Toggles the system to and from the speed control and torque control modes.
114
115
Deviation Counter Clear — Clears the Deviation Counter when operating in the Position Control mode.
116
117
Position Control Forward Limit LS — Connecting this terminal to CC will immediately stop the drive and hold its position.
If the connection remains, the drive will time-out and trip. This function is normally used for over-travel conditions.
Note: NO/NC = Normally Open/Normally Closed.
Note: Selection numbers are used when configuring the discrete input terminals via communications. They differentiate the Normally
Open and Normally Closed contact settings.
184
Terminal Selection Descriptions
F108
for additional information on this feature).
F108
F004
setting and assigns speed control to the Terminal Board.
F003
setting and assigns command control to the Terminal Board.
F108
for additional information on this feature).
WX9 ASD Installation and Operation Manual
to Store and setting an input
F354
for additional