F361
PID Feedback Delay Filter
Program Feedback Feedback Settings
This parameter determines the delay in the ASD output response to the motor-
control feedback signal (signal source is selected at PID Feedback Signal
Selection (F360)).
PID Feedback Proportional Gain
Program Feedback Feedback Settings
This parameter determines the degree that the Proportional function affects the
output signal. The larger the value entered here, the quicker the drive responds
to changes in feedback.
PID Feedback Integral Gain
Program Feedback Feedback Settings
This parameter determines the degree that the Integral function affects the
output signal. The smaller the value here, the more pronounced the effect of the
integral function on the output signal.
PID Deviation Upper Limit
Program Feedback Feedback Settings
This parameter determines the maximum amount that the feedback may
increase the output signal.
PID Deviation Lower Limit
Program Feedback Feedback Settings
This parameter determines the maximum amount that the feedback may
decrease the output signal.
PID Feedback Differential Gain
Program Feedback Feedback Settings
This parameter determines the degree that the Differential function affects the
output signal. The larger the value entered here, the more pronounced the affect
of the differential function for a given feedback signal level.
132
Direct Access Number — F361
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Direct Access Number — F362
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.0
Direct Access Number — F363
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.0
Direct Access Number — F364
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Direct Access Number — F365
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Direct Access Number — F366
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 2.55
WX9 ASD Installation and Operation Manual
F366