Toshiba WX9 ASD Installation & Operation Manual page 173

Table of Contents

Advertisement

F621
Cumulative Operation Time Alarm Setting
Program Protection Special Protection Parameters
This parameter sets a run-time value that, once exceeded, closes a contact. The
output signal may be used to control external equipment or used to engage a
brake.
Note:
The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).
Abnormal Speed Detection Time
Program Protection Abnormal Speed Settings
This parameter sets the time that an over-speed condition must exist to cause a
trip.
This parameter functions in conjunction with the settings of
Over-Speed Detection Frequency Upper Band (0 = disabled)
Program Protection Abnormal Speed Settings
This parameter sets the upper level of the Base Frequency range that, once
exceeded, will cause an Over-Speed Detected alert.
This parameter functions in conjunction with the settings of
Over-Speed Detection Frequency Lower Band (0 = disabled)
Program Protection Abnormal Speed Settings
This parameter sets the lower level of the Base Frequency range that, once
exceeded, will cause a Speed Drop Detected alert.
This parameter functions in conjunction with the settings of
Over-Voltage Limit Operation Level (fast)
Program Protection Stall
This parameter sets the upper DC bus voltage threshold that, once exceeded,
will cause an Over-Voltage Stall. An Over-Voltage Stall increases the output
frequency of the drive during deceleration for a specified time in an attempt to
prevent an Over-Voltage Trip.
If the over-voltage condition persists for more than 250 µS, an Over-Voltage
Trip will be incurred.
Note:
This feature may increase deceleration times.
WX9 ASD Installation and Operation Manual
Direct Access Number — F621
Parameter Type — Numerical
Factory Default — 175.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 999.9
Units — Hours (X 100)
Direct Access Number — F622
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — Yes
Minimum — 0.01
F623
and F624.
Maximum — 100.0
Units — Seconds
Direct Access Number — F623
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
F622
and F624.
Maximum — 30.0
Units — Hz
Direct Access Number — F624
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
F622
and F623.
Maximum — 30.00
Units — Hz
Direct Access Number — F625
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 50.00
Maximum — 250.0
Units — %
F625
161