F511
Deceleration Time 3
Program Special Acc/Dec (1 - 4) Settings
This parameter specifies the time for the drive to go from the Maximum
Frequency to 0.0 Hz for the Deceleration (Dec) 3 Profile.
The Acceleration/Deceleration (Acc/Dec) pattern may be set using F502.
The minimum Acceleration/Deceleration (Acc/Dec) time may be set using
F508.
Note:
A deceleration time that is shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Acceleration/Deceleration, Stall, and Ridethrough
settings may lengthen the deceleration time.
Acceleration/Deceleration Pattern 3
Program Special Acc/Dec (1 - 4) Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the Acceleration/
Deceleration (Acc/Dec) 3 parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Acceleration/Deceleration Switching Frequency 2
Program Special Acc/Dec Special
This parameter sets the frequency at which the acceleration control is switched
from the Acceleration (Acc) 2 Profile to the Acceleration (Acc) 3 Profile
during a multiple-profile configuration.
Acceleration Time 4
Program Special Acc/Dec (1 - 4) Settings
This parameter specifies the time for the drive to go from 0.0 Hz to the
Maximum Frequency for the Acceleration (Acc) 4 Profile. The
Acceleration/Deceleration (Acc/Dec) pattern may be set using F502. The
minimum Acc/Dec time may be set using F508.
Note:
An acceleration time that is shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Acceleration/Deceleration, Stall, and Ridethrough
settings may lengthen the acceleration time.
WX9 ASD Installation and Operation Manual
Direct Access Number — F511
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 6000.00
Units — Seconds
Direct Access Number — F512
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Direct Access Number — F513
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F514
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 6000.00
Units — Seconds