F010
Deceleration Time 1
Program Fundamental Acc/Dec 1 Settings
Program Special Acc/Dec (1 - 4) Settings
This parameter specifies the time in seconds for the drive to go from the
Maximum Frequency (F011) to 0.0 Hz for the Deceleration (Dec) 1 Profile.
The Acceleration/Deceleration (Acc/Dec) pattern may be set using F502.
When operating with the Automatic Acceleration/Deceleration Selection
(F000) enabled, the minimum Acc/Dec time may be set using F508.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Acceleration/Deceleration and Stall settings may
lengthen the acceleration time.
Maximum Frequency
Program Fundamental Frequency Settings
This setting determines the absolute maximum frequency that the ASD can
output.
Acceleration/Deceleration (Acc/Dec) times are calculated based on the
Maximum Frequency (F011) setting.
The Maximum Frequency is not limited by this setting while operating in the
Drooping Control mode (see
Note:
The maximum output frequency of the drive cannot be greater
than 10.5 times the base frequency, regardless of the Maximum
Frequency setting.
Note:
This setting may not be lower than the Upper-Limit Frequency
).
setting
(F012
Upper-Limit Frequency
Program Fundamental Frequency Settings
This parameter sets the highest frequency that the ASD will accept as a
frequency command or frequency setpoint. The ASD may output frequencies
higher than the Upper-Limit Frequency (but lower than the Maximum
Frequency) when operating in the PID Control mode, Torque Control mode,
or the Vector Control mode (sensorless or feedback).
Note:
This setting may not be higher than the Maximum Frequency
)
(F011
setting.
Lower-Limit Frequency
Program Fundamental Frequency Settings
This parameter sets the lowest frequency that the ASD will accept as a
frequency command or frequency setpoint.
The ASD will output frequencies lower than the Lower-Limit Frequency
when accelerating to the lower-limit or decelerating to a stop. Frequencies
below the Lower-Limit may also be output when operating in the PID Control
mode, Torque Control mode, or the Vector Control modes (sensorless or
feedback).
WX9 ASD Installation and Operation Manual
F320
for additional information on this setting).
Direct Access Number — F010
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum —
F508
Maximum — 6000
Units — Seconds
Direct Access Number — F011
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — No
Minimum — 30.0
Maximum — 299.0
Units — Hz
Direct Access Number — F012
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F013
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Upper-Limit Freq. (F012)
Units — Hz