Toshiba WX9 ASD Installation & Operation Manual page 112

Table of Contents

Advertisement

F203
VI/II Reference Point 2
Program Torque Setpoints
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the VI/II input terminals when
either terminal is used as the control input while operating in the Speed
Control or Torque Control mode.
This parameter sets the VI/II level that is associated with VI/II Point 2
Frequency when operating in the Speed control mode or is associated with the
VI/II Point 1 Torque when operating in the Torque Control mode.
This value is entered as 0% to 100% of the VI/II signal range.
See VI/II Reference Point 1
when used for Speed control.
See VI/II Point 1 Torque (F205) for additional information on this setting
when used for Torque Control.
VI/II Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the VI/II terminal when either
terminal is used as the control input while operating in the Speed Control
mode.
This parameter is the frequency that is associated with the setting of VI/II
Reference Point 2 (F203) when operating in the Speed Control mode.
See VI/II Reference Point 1
100
)
(F201
for additional information on this setting
)
(F201
for additional information on this setting.
Direct Access Number — F203
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F204
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Maximum Freq. (F011)
Units — Hz
WX9 ASD Installation and Operation Manual