F630
Brake Answer Waiting Time
Program Protection Special Protection Parameters
This parameter is used in conjunction with the discrete input terminal setting
64 [System Consistent Sequence (BA: braking answer)] (see item 64 of
10 on pg. 182
for additional information on this feature).
After activating the discrete input terminal System Consistent Sequence (B:
braking release), the setting of this parameter defines a window of time in
which 1) a Braking Answer response must be received, or 2) the brake must
release.
Should this timer setting expire before the Braking Answer is returned or the
brake releases, a Brake Fault (E-11) is incurred. Otherwise, the brake releases
and normal motor operations resume.
Brake Release After Run Timer
Program Protection Special Protection Parameters
This parameter sets the time that the brake will hold after the Run command
criteria has been met.
Earth Fault Alarm Level
Program Special Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Alarm activation criteria.
Earth Fault Alarm Time
Program Special Earth Fault
In the event that the Earth Fault Alarm activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Alarm is
activated.
This parameter sets the start-time of the count-down timer.
Earth Fault Trip Level
Program Special Earth Fault
This parameter sets the threshold level (%) that must be exceeded to meet the
Earth Fault Trip activation criteria.
WX9 ASD Installation and Operation Manual
Direct Access Number — F630
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Table
Minimum — 0.00
Maximum — 10.00
Units — Seconds
Direct Access Number — F632
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F640
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 0
Maximum — 100
Units — %
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F642
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 0.00
Maximum — 100
Units — %
F642
163