F105
Forward/Reverse Run Priority When Both Are Closed
Program Terminal Input Special Functions
The Forward/Reverse Priority Selection determines the operation of the ASD
if both the F and R control terminals are activated.
Settings:
0 — Reverse
1 — Suspend
The waveforms depict the motor response for all combinations of the F and R
terminal settings if the Reverse option is chosen.
The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.
Input Terminal Priority Selection
Program Terminal Input Special Functions
This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Terminal Board even though
the system is in the Hand mode.
With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Terminal Board will receive priority over
commands from the EOI.
See Jog Frequency
(F260)
function.
See
F250
F252
for additional information on DC Injection Braking.
Settings:
0 — Disabled
1 — Enabled
16-Bit Binary/BCD Input Selection
Program Terminal Input Special Functions
The Extended Terminal Function is used with the optional ASD-Multicom
card only. This parameter defines the format of the binary or BCD data when
using the option card.
Settings:
0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD
Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the Terminal Board as binary bits 0 – 3
The Frequency Mode 1 (F004) must be set to Binary/BCD (option).
For proper scaling of the binary or BCD input, parameters
configured [BIN Reference Point 1, BIN Point 1 Frequency, BIN Reference
Point 2, and BIN Point 2 Frequency].
80
for additional information on using the Jog
Direct Access Number — F105
Parameter Type — Selection List
Factory Default — Reverse
Changeable During Run — No
Direct Access Number — F106
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F107
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
(F115
– F118).
F228
F231
must be
WX9 ASD Installation and Operation Manual
F107