F275
Jump Frequency 3 Bandwidth
Program Special Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 3
(
F274).
Jump Frequency Processing Selection
Program Special Jump Frequencies
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See Jump Frequency 1
(F270)
Frequency settings.
Settings:
0 — Process Amount
1 — Output Frequency
Preset Speed 8
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed 8. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
Preset Speed 9
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed 9. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
Preset Speed 10
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1010 and is
identified as Preset Speed 10. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
118
for additional information on the Jump
F018
F018
F018
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Yes
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
for additional
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F288
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.00
for additional
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F289
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
for additional
Maximum — Upper-Limit Freq. (F012)
Units — Hz
WX9 ASD Installation and Operation Manual
F289