F275
Jump Frequency 3 Bandwidth
Program Special Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 3
(
F274).
Jump Frequency Processing Selection
Program Special Jump Frequencies
This parameter determines if the output frequency of the ASD or the PID
feedback signal will be used as a reference for determining the Jump
Frequency range.
See Jump Frequency 1
(F270)
Frequency settings.
Settings:
0 — Process Amount
1 — Output Frequency
Preset Speed 8
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed 8. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
Preset Speed 9
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1001 and is
identified as Preset Speed 9. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
Preset Speed 10
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 1010 and is
identified as Preset Speed 10. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
118
for additional information on the Jump
F018
F018
F018
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Direct Access Number — F276
Parameter Type — Selection List
Factory Default — Process Amount
Changeable During Run — Yes
Direct Access Number — F287
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
for additional
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F288
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.00
for additional
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F289
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
for additional
Maximum — Upper-Limit Freq. (F012)
Units — Hz
WX9 ASD Installation and Operation Manual
F289