F653
Deceleration Time Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Deceleration Time. Selecting either VI/II or RR enables this
feature. The selected input is used as a modifier of the programmed
Deceleration Time setting.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Torque Boost Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Torque Boost setting. Selecting either VI/II or RR enables
this feature. The selected input is used as a modifier of the programmed Torque
Boost setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Adding Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a modifier of the programmed Output Frequency.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — CN8 Option
6 — Binary/BCD (Option)
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Option Board
10 — UP/DOWN Frequency
11 — Pulse Input (Option)
WX9 ASD Installation and Operation Manual
Direct Access Number — F653
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F654
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F660
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes