Toshiba WX9 ASD Installation & Operation Manual page 126

Table of Contents

Advertisement

F243
End Frequency
Program Special Frequency Control
This parameter sets the lowest frequency that the drive will recognize during
deceleration before going to 0.0 Hz.
Dead Band of 0Hz Frequency Setting Signal
Program Special Special Parameters
This parameter sets an output frequency threshold that, until the commanded
frequency surpasses this setting, the ASD will output 0.0 Hz to the motor.
Note:
This setting will override the Start Frequency setting (F240) if
this setting has a higher value.
DC Injection Braking Start Frequency
Program Protection DC Braking
During deceleration, this is the frequency at which DC Injection Braking will
start.
DC Injection Braking
DC Injection Braking is a braking system used with three-phase motors.
Unlike conventional brakes, there is no physical contact between the rotating
shaft and a stationary brake pad or drum. When braking is required, the drive
outputs a DC current that is applied to the windings of the motor to quickly
brake the motor. The braking current stops when the time entered at DC
Injection Braking Time (F252) times out.
The intensity of the DC current used while braking determines how fast the
motor will come to a stop and may be set at DC Injection Braking Current
(F251). The intensity setting is entered as a percentage of the full load current
of the ASD.
DC Injection Braking is also used to preheat the motor or to keep the rotor
from spinning freely when the motor is off by providing a pulsating DC current
into the motor at the Carrier Frequency. This feature may be enabled at
Motor Shaft Fixing Control (F254).
DC Injection Braking Current
Program Protection DC Braking
This parameter sets the percentage of the rated current of the drive that will be
used for DC Injection Braking. A larger load will require a higher setting.
114
Direct Access Number — F243
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F244
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 5.0
Units — Hz
Direct Access Number — F250
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 120.0
Units — Hz
Direct Access Number — F251
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.0
Units — %
WX9 ASD Installation and Operation Manual
F251