F016
Manual Torque Boost 1
Program Fundamental Motor Set 1
Program Motor Motor Set 1
The Manual Torque Boost 1 function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the Base Frequency 1 (F014) setting.
The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.
Note:
Setting an excessive Torque Boost level may cause nuisance
tripping and mechanical stress to loads.
Motor Overload Protection Configuration
Program Protection Overload
This parameter is used to protect the motor from an over-current condition.
This parameter setting may extend the Over-Voltage Limit Operation (F305)
time settings.
This parameter may be affected by the setting of the Power Running Stall
Continuous Trip Detection Time (F452).
Settings:
Setting
Type of Motor Trip
0
Motor OL Trip
1
Motor OL Trip
2
Without Motor OL Trip
3
4
V/f Motor OL Trip
5
V/f Motor OL Trip
6
V/f Motor Without OL Trip
7
V/f Motor Without OL Trip
WX9 ASD Installation and Operation Manual
Soft Stall Setting
Without Soft Stall
With Soft Stall
Without Soft Stall
Soft Stall Only
No Soft Stall
With Soft Stall
Without Soft Stall
With Soft Stall Only
Direct Access Number — F016
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
Direct Access Number — F017
Parameter Type — Selection List
Factory Default — Motor OL Trip
without Soft Stall
Changeable During Run — No
F017
75