F194
V/f Five-Point 3 Frequency
Program Special V/f Five-Point Setting
The V/f Five-Point 3 Frequency sets the frequency to be associated with the
V/f Five-Point 3 Voltage (F195).
See V/f Five-Point 1 Frequency (F190) for additional information on custom
V/f curves.
V/f Five-Point 3 Voltage
Program Special V/f Five-Point Setting
The V/f Five-Point 3 Voltage establishes the percentage of the output voltage
that is to be associated with the frequency setting of the V/f Five-Point 3
Frequency (F194).
The Current/Voltage Units Setup (F701) setting will determine if the
selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
The default setting is %.
See V/f Five-Point 1 Frequency
V/f curves.
V/f Five-Point 4 Frequency
Program Special V/f Five-Point Setting
The V/f Five-Point 4 Frequency sets the frequency to be associated with the
V/f Five-Point 4 Voltage (F197).
See V/f Five-Point 1 Frequency
V/f curves.
V/f Five-Point 4 Voltage
Program Special V/f Five-Point Setting
The V/f Five-Point 4 Voltage establishes the percentage of the output voltage
that is to be associated with the frequency setting of V/f Five-Point 4
Frequency (F196).
The Current/Voltage Units Setup (F701) setting will determine if the
selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
The default setting is %.
See V/f Five-Point 1 Frequency (F190) for additional information on custom
V/f curves.
V/f Five-Point 5 Frequency
Program Special V/f Five-Point Setting
The V/f Five-Point 5 Frequency sets the frequency to be associated with the
V/f Five-Point 5 Voltage (F199).
See V/f Five-Point 1 Frequency
V/f curves.
WX9 ASD Installation and Operation Manual
(F190)
for additional information on custom
(F190)
for additional information on custom
(F190)
for additional information on custom
Direct Access Number — F194
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Direct Access Number — F195
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F196
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Direct Access Number — F197
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F198
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
F198
97