Toshiba WX9 ASD Installation & Operation Manual page 110

Table of Contents

Advertisement

F199
V/f Five-Point 5 Voltage
Program Special V/f Five-Point Setting
The V/f Five-Point 5 Voltage establishes the percentage of the output voltage
that is to be associated with the frequency setting of the V/f Five-Point 5
Frequency (F198).
The Current/Voltage Units Setup
selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
The default setting is %.
See V/f Five-Point 1 Frequency (F190) for additional information on custom
V/f curves.
Frequency Priority Selection
Program Fundamental Standard Mode Selection
Either Frequency Mode 1 or Frequency Mode 2 may control the output
frequency of the ASD. This parameter determines which of the two will control
the output frequency and the conditions in which control will be switched from
one to the other.
Settings:
0 — Frequency Source 1
1 — Frequency Source 2
2 — Frequency Source 1 Priority
3 — Frequency Source 2 Priority
4 — Frequency Source Priority Switching
The Frequency Source 1 or Frequency Source 2 setting specifies the source
of the input frequency command signal. These settings are performed at
Frequency Mode 1
(F004)
If Frequency Source 1 is selected here, the ASD will follow the settings of
Frequency Mode 1 (F004). If Frequency Source 2 is selected here, the ASD
will follow the settings of Frequency Mode 2 (F207).
If Frequency Source 1 Priority is selected here, the ASD will follow the
control of the Frequency Mode 1 setting for the duration that the commanded
frequency of Frequency Mode 1 exceeds the
frequency of Frequency Mode 1 is less than or equal to the setting of F208, the
ASD will follow the setting of Frequency Mode 2.
If Frequency Source 2 Priority is selected here, the ASD will follow the
control of the Frequency Mode 2 setting for the duration that the commanded
frequency of Frequency Mode 2 exceeds the Frequency Mode Priority
Switching Frequency
(F208)
Frequency Mode 2 is less than or equal to the setting of F208, the ASD will
follow the setting of Frequency Mode 1.
If Frequency Source Priority Switching is selected here, the ASD will follow
the control of the discrete input terminal assigned the function of Terminal
Frequency Priority. The discrete terminal Terminal Frequency Priority will
toggle control to and from the Frequency Mode 1 and Frequency Mode 2
selections for the duration of each activation/deactivation.
98
(F701)
setting will determine if the
and Frequency Mode 2 (F207), respectively.
F208
setting. If the commanded
setting. If the commanded frequency of
Direct Access Number — F199
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F200
Parameter Type — Selection List
Factory Default — Frequency Source 1
Changeable During Run — Yes
WX9 ASD Installation and Operation Manual
F200

Advertisement

Table of Contents
loading

Table of Contents