F610
Low-Current Trip Selection
Program Protection Low-Current Settings
This parameter Enables/Disables the low-current trip feature.
When enabled, the drive will trip on a low-current fault if the output current of
the drive falls below the level defined at
at F612.
Settings:
0 — Disabled
1 — Enabled
Low-Current Detection Current
Program Protection Low-Current Settings
When the Low-Current Trip Selection (F610) is enabled, this function sets the
low-current trip threshold.
The threshold value is entered as a percentage of the maximum rating of the
drive.
Low-Current Detection Time
Program Protection Low-Current Settings
When the Low-Current Trip Selection (F610) is enabled, this function sets the
time that the low-current condition must exist to cause a trip.
Short Circuit Detection at Start
Program Protection Special Protection Parameters
This parameter determines when the system will perform an Output Short
Circuit test.
Note:
Selection 3 is recommended for high-speed motor applications.
Because of the low impedance of high-speed motors, the
standard-pulse setting may result in a motor malfunction.
Settings:
0 — Check at Every Run
1 — Check at Only Power On or Reset
Short Circuit Pulse Run Duration
Program Protection Special Protection Parameters
This parameter sets the pulse width of the ASD output pulse that is applied to
the motor during an Output Short Circuit test.
WX9 ASD Installation and Operation Manual
F611
and remains there for the time set
Direct Access Number — F610
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F611
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Direct Access Number — F612
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Units — Seconds
Direct Access Number — F613
Parameter Type — Selection List
Factory Default — Check at Every Run
Changeable During Run — No
Direct Access Number — F614
Parameter Type — Numerical
Factory Default — 50
Changeable During Run — No
Minimum — 1
Maximum — 100
Units — µS
F614
159