F210
RR Reference Point 1
Program Torque Setpoints
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
This parameter sets the RR input level that is associated with the RR Point 1
Frequency setting when operating in the Speed control mode or is associated
with the RR Input Point 1 Torque setting when operating in the Torque
Control mode.
The bias and gain of the RR terminal may be trimmed at
respectively.
RR Speed Control Setup
Perform the following setup to allow the system to perform Speed control from
the RR terminal:
Set RR Point 1 Frequency (F211).
Set RR Reference Point 1 (F210) — the input analog signal level that
corresponds to the frequency setting at RR Point 1 Frequency.
Set RR Point 2 Frequency (F213).
Set RR Reference Point 2 (F212) — the input analog signal level that
corresponds to the frequency setting at RR Point 2 Frequency.
Program Fundamental Standard Mode Selection Frequency
Mode 1 RR
Program Fundamental Standard Mode Selection Command
Mode Selection Terminal Board
Provide a Run command (F and/or R).
Once set, as the RR voltage changes, the output frequency of the drive will vary
in accordance with the above settings.
This parameter value is entered as 0% to 100% of the RR signal range.
RR Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control
mode.
This parameter sets the RR Point 1 Frequency and is the frequency that is
associated with the setting of RR Reference Point 1 (F210) when operating in
the Speed Control mode.
See RR Reference Point 1
RR Reference Point 2
Program Torque Setpoints
Program Frequency Speed Reference Setpoints
This parameter is used to set the gain and bias of the RR input terminal when
this terminal is used as the control input while operating in the Speed Control or
the Torque Control mode.
This parameter sets the RR input level that represents RR Reference Point 2
(frequency) (torque or frequency).
This value is entered as 0 – 100% of the 0 – 10 VDC RR input signal range.
See RR Reference Point 1
WX9 ASD Installation and Operation Manual
F472
)
(F210
for additional information on this setting.
(F210)
for additional information on this setting.
Direct Access Number — F210
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
Frequency Settings
and F473,
Direct Access Number — F211
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F212
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
F212