Toshiba WX9 ASD Installation & Operation Manual page 104

Table of Contents

Advertisement

F165
OUT6 Off Delay
Program Terminal Output Terminal Delays
This parameter delays the opening of the OUT6 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to prevent relay chatter.
OUT7 Off Delay
Program Terminal Output Terminal Delays
This parameter delays the opening of the OUT7 output terminals by the
programmed value (see waveforms at F160).
The delay may be increased to prevent relay chatter.
Base Frequency 2
Program Motor Motor Set 2
The Base Frequency 2 setting is the frequency at which the output voltage of
the ASD reaches its maximum setting. The Base Frequency Voltage 2
parameter is set at F171.
This parameter is used only when the parameters for Motor Set 2 are
configured and selected. Motor Set 2 may be selected by a properly configured
input terminal (see
Table 10 on pg.
For proper motor operation, the Base Frequency should be set for the name-
plated frequency of the motor.
Base Frequency Voltage 2
Program Motor Motor Set 2
The Base Frequency Voltage 2 is the Motor 2 output voltage at the Base
Frequency 2 (F170). Regardless of the programmed value, the output voltage
cannot be higher than the input voltage.
The actual output voltage will be influenced by the input voltage of the ASD
and the Supply Voltage Compensation setting (F307).
This parameter is used only when the parameters for Motor Set 2 are
configured and selected. Motor Set 2 may be selected by a properly configured
input terminal (see
Table 10 on pg.
Manual Torque Boost 2
Program Motor Motor Set 2
The Manual Torque Boost 2 function is used to increase the low frequency
torque for high inertia loads by increasing the output voltage at frequencies
below ½ of the Base Frequency 2 setting (F170).
See
F016
(Manual Torque Boost 1) for an explanation of torque boost.
This parameter is used only when the parameters for Motor Set 2 are
configured and selected. Motor Set 2 may be selected by a properly configured
input terminal (see
Table 10 on pg.
92
182).
182).
182).
Direct Access Number — F165
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F166
Parameter Type — Numerical
Factory Default — 2.0
Changeable During Run — No
Minimum — 2.0
Maximum — 200.0
Units — mS
Direct Access Number — F170
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 25.0
Maximum — 299.0
Units — Hz
Direct Access Number — F171
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 600.0
Units — Volts
Direct Access Number — F172
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.0
Maximum — 30.0
Units — %
WX9 ASD Installation and Operation Manual
F172