F103
ST Signal Selection
Program Terminal Input Special Functions
This parameter is used to set the operation of the Standby (ST) control terminal
or any terminal configured as the ST terminal.
Settings:
0 — Standard
1 — Always On
2 — Interlock with F/R Terminal
The Standard setting enables the ASD for operation so long as the control
terminal ST is connected to CC via a jumper, contact, or other means.
The Always On setting allows the ASD to operate without the ST-to-CC
connection. The control terminal ST may be configured for another function or
unused.
The Interlock with F/R Terminal setting configures the F (Forward) and R
(Reverse) control terminals for the secondary function of Standby. Closing a
set of contacts to either F or R will cause the ASD to accelerate the motor to the
programmed setpoint of F or R. Opening the F and R contact will disable the
ASD and the motor will coast to a stop. The control terminal ST may be
configured for another function or unused.
WX9 ASD Installation and Operation Manual
Direct Access Number — F103
Parameter Type — Selection List
Factory Default — Standard
Changeable During Run — No
F103
79