F103
ST Signal Selection
Program Terminal Input Special Functions
This parameter is used to set the operation of the Standby (ST) control terminal
or any terminal configured as the ST terminal.
Settings:
0 — Standard
1 — Always On
2 — Interlock with F/R Terminal
The Standard setting enables the ASD for operation so long as the control
terminal ST is connected to CC via a jumper, contact, or other means.
The Always On setting allows the ASD to operate without the ST-to-CC
connection. The control terminal ST may be configured for another function or
unused.
The Interlock with F/R Terminal setting configures the F (Forward) and R
(Reverse) control terminals for the secondary function of Standby. Closing a
set of contacts to either F or R will cause the ASD to accelerate the motor to the
programmed setpoint of F or R. Opening the F and R contact will disable the
ASD and the motor will coast to a stop. The control terminal ST may be
configured for another function or unused.
WX9 ASD Installation and Operation Manual
Direct Access Number — F103
Parameter Type — Selection List
Factory Default — Standard
Changeable During Run — No
F103
79