Toshiba WX9 ASD Installation & Operation Manual page 150

Table of Contents

Advertisement

F393
Preset Speed 13 (Direction)
Program Frequency Preset Speed Modes
Determines the forward/reverse setting for the Preset Speed 13
Settings:
Forward
Reverse
Preset Speed 14 (Direction)
Program Frequency Preset Speed Modes
Determines the forward/reverse setting for the Preset Speed 14
Settings:
Forward
Reverse
Preset Speed 15 (Direction)
Program Frequency Preset Speed Modes
Determines the forward/reverse setting for the Preset Speed 15
Settings:
Forward
Reverse
Autotune and Reset Configuration
Program Motor Vector Motor Model
This parameter sets the Autotune command status.
Settings:
0 — Autotune Disabled
1 — Reset Motor Defaults
2 — Perform Autotune on Run Command
Slip Frequency Gain
Program Motor Vector Motor Model
This parameter provides a degree of slip compensation for a given load. A
higher setting here decreases the slip allowed for a given load/ASD output ratio.
Motor Constant 1 (primary resistance)
Program Motor Vector Motor Model
This parameter is the measurement of the stator resistance and is considered a
Motor Constant (unchanging). This value is used in conjunction with other
constants to tune the motor.
To use Vector Control, Automatic Torque Boost, or Automatic Energy-
Saving, the Motor Constant setting (motor tuning) is required.
138
Direct Access Number — F393
Parameter Type — Selection List
Factory Default — Forward
(
F292).
Changeable During Run — No
Direct Access Number — F394
Parameter Type — Selection List
Factory Default — Forward
(
F293).
Changeable During Run — No
Direct Access Number — F395
Parameter Type — Selection List
Factory Default — Forward
(
F294).
Changeable During Run — No
Direct Access Number — F400
Parameter Type — Selection List
Factory Default — Autotune Disabled
Changeable During Run — No
Direct Access Number — F401
Parameter Type — Numerical
Factory Default — 0.60
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.55
Direct Access Number — F402
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — No
Minimum — 0.0
Maximum — 100,000 M
Units — M