F018
Preset Speed 1
Program Frequency Preset Speeds
Up to 15 output frequency values that fall within the Lower-Limit and the
Upper-Limit range may be programmed into the drive and output as a Preset
Speed. This parameter assigns an output frequency to binary number 0001 and
is identified as Preset Speed 1. The binary number is applied to S1 – S4 of the
Terminal Board to output the Preset Speed.
Perform the following setup to allow the system to receive Preset Speed
control input at the S1 – S4 terminals:
Program Fundamental Standard Mode Selection Command
1.
Mode Selection Terminal Board
Program Terminal Input Terminals S1 (set to Preset Speed 1;
2.
LSB of 4-bit count). Repeat for S2 – S4 (MSB of 4-bit count) as Preset
Speed 2 – 4, respectively (all Normally Open).
Note: The default setting of S4 is EOff, but this terminal may be
re-assigned as the MSB.
Program Frequency Preset Speeds Preset Speed 1 (press Enter
3.
twice and set an output frequency as Preset Speed 1; repeat for Preset
Speeds 2 – 15 as required).
Program Preset Speed Modes Preset Speed Operation Mode 
4.
Enabled/Disabled
Select Enabled to use the direction, acceleration/deceleration, and
torque settings of the Preset Speed being run. The torque settings used
will be as defined in
discrete input terminals V/f Switching 1 and 2 in
5.
Place the system in the Auto mode (Hand/Auto LED Off).
6.
Provide a Run command (connect F and/or R to CC).
Connect S1 to CC to run Preset Speed 1 (S1 to CC = 0001 binary).
With S1 – S4 configured to output Preset Speeds
may be applied to S1 – S4 of the Terminal Board to run the associated Preset
Speed. If bidirectional operation is required, F and R must be connected to CC,
and Preset Speed Operation Mode must be set to Enabled at F380.
With S1 being the least significant bit of a binary count, the S1 – S4 settings
will produce the programmed speed settings as indicated in the Preset Speed
Truth Table to the right.
Preset Speeds are also used in the Pattern Run mode.
Preset Speed 2
Program Frequency Preset Speeds
This parameter assigns an output frequency to binary number 0010 and is
identified as Preset Speed 2. The binary number is applied to S1 – S4 of the
Control Terminal Strip to output the Preset Speed (see
information on this parameter).
76
F170
-
F181
and as selected via the associated
Table 10 on pg.
(F115
– F118), 0001 – 1111
F018
Direct Access Number — F018
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Preset Speed Truth Table
S4
Preset
MSB
1
2
3
4
5
6
7
8
9
10
11
12
13
182.
14
15
Note: 1 = Terminal connected to CC.
Direct Access Number — F019
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0
for additional
Maximum — Upper-Limit Freq. (F012)
Units — Hz
WX9 ASD Installation and Operation Manual
F019
S1
S3
S2
Output
LSB
0
0
0
1
F018
0
0
1
0
F019
0
0
1
1
F020
0
1
0
0
F021
0
1
0
1
F022
0
1
1
0
F023
0
1
1
1
F024
1
0
0
0
F287
1
0
0
1
F288
1
0
1
0
F289
1
0
1
1
F290
1
1
0
0
F291
1
1
0
1
F292
1
1
1
0
F293
1
1
1
1
F294