F515
Deceleration Time 4
Program Special Acc/Dec (1 - 4) Settings
This parameter specifies the time for the drive to go from the Maximum
Frequency to 0.0 Hz for the Deceleration (Dec) 4 Profile. The Acceleration/
Deceleration (Acc/Dec) pattern may be set using F502. The minimum Acc/Dec
time may be set using F508.
Note:
A deceleration time that is shorter than the load will allow may
cause nuisance tripping and mechanical stress to loads.
Automatic Acceleration/Deceleration, Stall, and Ridethrough
settings may lengthen the deceleration time.
Acceleration/Deceleration Pattern 4
Program Special Acc/Dec (1 - 4) Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the Acceleration/
Deceleration (Acc/Dec) 4 parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Acceleration/Deceleration Switching Frequency 3
Program Special Acc/Dec Special
This parameter sets the frequency at which the acceleration control is switched
from the Acceleration (Acc) 3 Profile to the Acceleration (Acc) 4 Profile
during a multiple-profile configuration.
Motor Overload Protection Level 1
Program Fundamental Motor Set 1
Program Motor Motor Set 1
The Motor Overload Protection Level 1 parameter specifies the motor
overload current level for Motor Set 1. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it may be set
as a percentage of the ASD rating. The nameplated FLA of the motor may be
entered directly when Amps is selected as the unit of measurement (see
Current/Voltage Units Setup (F701) to change the display unit).
Motor Overload Protection Level settings (1 – 4) will be displayed in Amps
if the EOI display units are set to V/A rather than %.
156
Direct Access Number — F515
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 6000.00
Units — Seconds
Direct Access Number — F516
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Direct Access Number — F517
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F600
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %