F702
Free Unit Multiplication Factor (0 = off)
Program Utilities Display Parameters
This parameter provides a multiplier for the displayed speed value shown on the
EOI of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).
Example: An output frequency of 100 Hz would be displayed as 50 Hz if using
a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters (i.e., F364, F365, F367, and
F368) are not affected by this setting.
Free Unit Selection
Program Utilities Display Parameters
The parameter sets the number of decimal places to be displayed during non-
Acceleration/Deceleration (Acc/Dec) functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Acceleration/Deceleration Unit Time Setup
Program Utilities Display Parameters
This parameter sets the number of decimal places to be displayed for
Acceleration/Deceleration (Acc/Dec) functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Prohibit Initializing User Parameters During Typeform
Initialization
Program Utilities Prohibition
This parameter Enables/Disables the ability to initialize user parameters during
a Type Form initialization.
Settings:
0 — Enabled
1 — Disabled
CN8 Option Override Multiplication Gain
Program Feedback Override Control
If operating using the CN8 Option, this parameter provides a value to be used
in the event that Setting is selected for the Multiplying Input Selection
(F661).
WX9 ASD Installation and Operation Manual
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
Direct Access Number — F703
Parameter Type — Selection List
Factory Default — 0.1
Changeable During Run — Yes
Direct Access Number — F704
Parameter Type — Selection List
Factory Default — 0.1
Changeable During Run — Yes
Direct Access Number — F709
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — 100.00
Units — %
F729
169