F702
Free Unit Multiplication Factor (0 = off)
Program Utilities Display Parameters
This parameter provides a multiplier for the displayed speed value shown on the
EOI of the ASD.
This parameter may be used to display the rate that a commodity is being
processed by the driven load in process units (i.e., units/time).
Example: An output frequency of 100 Hz would be displayed as 50 Hz if using
a multiplier of 0.5 for this parameter.
Note:
PID frequency-limiting parameters (i.e., F364, F365, F367, and
F368) are not affected by this setting.
Free Unit Selection
Program Utilities Display Parameters
The parameter sets the number of decimal places to be displayed during non-
Acceleration/Deceleration (Acc/Dec) functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Acceleration/Deceleration Unit Time Setup
Program Utilities Display Parameters
This parameter sets the number of decimal places to be displayed for
Acceleration/Deceleration (Acc/Dec) functions.
Settings:
0 — 1
1 — 0.1
2 — 0.01
Prohibit Initializing User Parameters During Typeform
Initialization
Program Utilities  Prohibition
This parameter Enables/Disables the ability to initialize user parameters during
a Type Form initialization.
Settings:
0 — Enabled
1 — Disabled
CN8 Option Override Multiplication Gain
Program Feedback Override Control
If operating using the CN8 Option, this parameter provides a value to be used
in the event that Setting is selected for the Multiplying Input Selection
(F661).
WX9 ASD Installation and Operation Manual
Direct Access Number — F702
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — Hz/UDU
Direct Access Number — F703
Parameter Type — Selection List
Factory Default — 0.1
Changeable During Run — Yes
Direct Access Number — F704
Parameter Type — Selection List
Factory Default — 0.1
Changeable During Run — Yes
Direct Access Number — F709
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — 100.00
Units — %
F729