F191
V/f Five-Point 1 Voltage
Program Special V/f Five-Point Setting
The V/f Five-Point 1 Voltage establishes the percentage of the output voltage
that is to be associated with the frequency setting of
Frequency).
The Current/Voltage Units Setup
screen selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
If using Voltage as a unit of measure and with no voltage correction (Supply
Voltage Correction (F307) Disabled), the limit of the on-screen display value
for this parameter is 575.00 Volts.
If using % as a unit of measure and with no voltage correction (Supply
Voltage Correction (F307) Disabled), the ASD output voltage will be the
percentage setting multiplied by the ASD-rated voltage.
See V/f Five-Point 1 Frequency (F190) for additional information on this
setting
V/f Five-Point 2 Frequency
Program Special V/f Five-Point Setting
The V/f Five-Point 2 Frequency sets the frequency to be associated with the
V/f Five-Point 2 Voltage (F193).
See V/f Five-Point 1 Frequency
V/f curves.
V/f Five-Point 2 Voltage
Program Special V/f Five-Point Setting
The V/f Five-Point 2 Voltage establishes the percentage of the output voltage
that is to be associated with the frequency setting of
Frequency).
The Current/Voltage Units Setup
selection for this parameter appears in the form of a Voltage (V) or as a
Percentage (%) of the ASD rating.
The default setting is %.
See V/f Five-Point 1 Frequency
setting.
96
F190
(V/f Five-Point 1
(F701)
setting will determine if the on-
(F190)
for additional information on custom
F192
(V/f Five-Point 2
(F701)
setting will determine if the
(F190)
for additional information on this
Direct Access Number — F191
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F192
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
WX9 ASD Installation and Operation Manual