Toshiba WX9 ASD Installation & Operation Manual page 107

Table of Contents

Advertisement

F181
Motor Overload Protection Level 4
Program Motor Motor Set 4
The Motor Overload Protection Level 4 parameter specifies the motor
overload current level for Motor Set 4. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps (V/A) or it
may be set as a percentage of the ASD rating. The name-plated FLA of the
motor may be entered directly when Amps is selected as the unit of
measurement (see Current/Voltage Units Setup
unit).
Motor Overload Protection Level settings (1 – 4) will be displayed in Amps
if the EOI display units are set to V/A rather than %.
V/f Adjustment Coefficient
Program Special Special Parameters
This parameter may be used in the Constant Torque or the Variable Torque
modes only and should be adjusted gradually to improve the application-
specific torque requirements. The Manual Torque Boost 1 setting (F016) may
be adjusted to improve the low-frequency torque performance.
Note:
The Torque Boost setting should be adjusted gradually before
attempting performance corrections using this parameter.
V/f Five-Point 1 Frequency
Program Special V/f Five-Point Setting
The V/f Five-Point 1 Frequency setting establishes the frequency that is to be
associated with the voltage setting of
The V/f Five-Point settings define a custom volts per hertz relationship for the
startup output of the ASD.
To enable this function, set the V/f Pattern (F015) selection to V/f Five-Point
Setting.
V/f Curves may be useful in starting high inertia loads such as rotary drum
vacuum filters.
WX9 ASD Installation and Operation Manual
(F701)
to change the display
F191
(V/f Five-Point 1 Voltage).
Direct Access Number — F181
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Direct Access Number — F183
Parameter Type — Numerical
Factory Default — 32
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Direct Access Number — F190
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 299
Units — Hz
F190
95