Toshiba WX9 ASD Installation & Operation Manual page 179

Table of Contents

Advertisement

F671
AM Output Terminal Adjustment
Program Terminal Analog Output Terminals
This function is used to calibrate the AM analog output terminal.
To calibrate the AM analog output, connect a meter (current or voltage) as
described at F670.
With the drive running at a known frequency, adjust this parameter until the
running frequency produces the desired DC level output at the FM terminal.
MON 1 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter sets the MON1 analog output terminal. Possible assignments
for this output terminal are listed in
The MON1 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
MON1 Terminal Meter Setup Parameters
F672 — MON1 Terminal Meter Selection
F673 — MON1 Terminal Meter Adjustment
MON 1 Terminal Meter Adjustment
Program Terminal Analog Output Terminals
This parameter is used to set the gain of the MON1 output terminal and is used
in conjunction with the settings of MON1 Terminal Meter Selection (F672).
See MON1 Terminal Meter Selection (F672) for additional information on
this setting.
MON 2 Terminal Meter Selection
Program Terminal Analog Output Terminals
This parameter is used to set the output function of the MON2 analog output
terminal. The available assignments for this output terminal are listed in
on pg.
181.
The MON2 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
additional information on the function of this terminal.
MON2 Terminal Meter Setup Parameters
F674 — MON2 Terminal Meter Selection
F675 — MON2 Terminal Meter Adjustment
WX9 ASD Installation and Operation Manual
Table 11 on pg.
186.
Direct Access Number — F671
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F672
Parameter Type — Selection List
Factory Default — Output Voltage
Changeable During Run — Yes
Direct Access Number — F673
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F674
Parameter Type — Selection List
Factory Default — Compensated
Table 9
Changeable During Run — Yes
F674
Frequency
167