F367
Number of PG Input Pulses
Program Feedback PG Settings
This parameter is used to set the end-of-travel range when using an encoder on
a motor-driven positioning system (e.g., hoist/crane, etc.).
Note:
The PG Vector Feedback Board option is required to use this
feature.
Selection of Number of PG Input Phases
Program Feedback PG Settings
This parameter determines the type of information that is supplied by the phase
encoder.
Note:
The PG Vector Feedback Board option is required to use this
feature.
Settings:
1 — Single Phase
2 — Two Phase
PG Disconnection Detection
Program Feedback PG Settings
This parameter Enables/Disables the system's monitoring of the PG connection
status when using encoders with line driver outputs.
Note:
The PG Vector Feedback Board option is required to use this
feature.
Settings:
0 — Disabled
1 — Enabled
Electronic Gear Setting (pulses/rotations)
Program Feedback PG Settings
This parameter sets the number of pulses per revolution when using a shaft-
mounted encoder and the PG Option Board for closed loop speed control.
WX9 ASD Installation and Operation Manual
Direct Access Number — F367
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 1
Maximum — 9999
Units — Pulse Count
Direct Access Number — F368
Parameter Type — Selection List
Factory Default — Two Phase
Changeable During Run — No
Direct Access Number — F369
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F370
Parameter Type — Numerical
Factory Default — 1000
Changeable During Run — Yes
Minimum — 100
Maximum — 4000
F370