Toshiba WX9 ASD Installation & Operation Manual page 187

Table of Contents

Advertisement

F814
Point 2 Frequency
Program Communications Communication Adjustments
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See Point 1 Setting
(F811)
This parameter sets the Communications Point 2 Frequency.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Baud Rate (RS232/RS485)
Program Communications Communication Settings
This parameter sets the RS232/RS485 baud rate.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Settings:
1 — 1200
2 — 2400
3 — 4800
4 — 9600
5 — 19200
6 — 38400
RS485 Wire Count
Program Communications Communication Settings
This parameter sets the communications protocol to the 2- or 4-wire method.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Settings:
0 — 2 wire
1 — 4 wire
Send Waiting Time (RS232/RS485)
Program Communications Communication Settings
This parameter sets the RS232/RS485 response delay time.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
WX9 ASD Installation and Operation Manual
for additional information on this setting.
Direct Access Number — F814
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Maximum Freq. (F011)
Units — Hz
Direct Access Number — F820
Parameter Type — Selection List
Factory Default — 9600
Changeable During Run — Yes
Direct Access Number — F821
Parameter Type — Selection List
Factory Default — 2 wire
Changeable During Run — Yes
Direct Access Number — F825
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F825