F223
RX2 Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets RX2 Point 1 Frequency and is the frequency that is
associated with the setting of RX2 Reference Point 1 (F222).
See RX2 Reference Point 1
RX2 Reference Point 2
Program Torque Setpoints
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control or the Torque Control mode.
This parameter sets the RX2 input level that represents RX2 Reference Point 2
(frequency) (direction/torque/frequency). This value is entered as 
-100 to +100% of the -10 to +10 VDC RX2 input signal range.
See RX2 Reference Point 1
RX2 Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the RX2 input
terminal when this terminal is used as the control input while operating in the
Speed Control mode.
This parameter sets RX2 Point 2 Frequency and is the frequency that is
associated with the setting of RX2 Reference Point 2 (F224).
See RX2 Reference Point 1
108
(F222)
for additional information on this setting.
(F222)
for additional information on this setting.
(F222)
for additional information on this setting.
Direct Access Number — F223
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — - (Maximum Freq. (F011))
Maximum — + (Maximum Freq. (F011))
Units — Hz
Direct Access Number — F224
Parameter Type — Numerical
Factory Default — +100.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — +100.0
Units — %
Direct Access Number — F225
Parameter Type — Numerical
Factory Default — +60.0
Changeable During Run — Yes
Minimum — - (Maximum Freq. (F011))
Maximum — + (Maximum Freq. (F011))
Units — Hz