F230
BIN Reference Point 2
Program Torque Setpoints
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control or the Torque Control mode.
This parameter sets BIN Reference Point 2 (direction/torque/frequency) and is
entered as 0 to 100% of the BIN binary input word 11111111 (255
See BIN Reference Point 1
BIN Point 2 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
This parameter sets BIN Point 2 Frequency and is the frequency that is
associated with the setting of BIN Reference Point 2 (F230).
See BIN Reference Point 1
BIN Input Point 1 Torque
Program Torque Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input and motor load.
This parameter sets BIN Input Point 1 Torque and is entered as 
-250 to +250% of the rated torque.
See BIN Reference Point 1 (F228) for additional information on this setting.
BIN Input Point 2 Torque
Program Torque Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input and motor load.
This parameter sets BIN Input Point 2 Torque and is entered as 
-250 to +250% of the rated torque.
See BIN Input Point 1 Torque (F232) for additional information on this
setting.
WX9 ASD Installation and Operation Manual
(F228)
for additional information on this setting.
)
(F228
for additional information on this setting.
Direct Access Number — F230
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
).
D
Direct Access Number — F231
Parameter Type — Numerical
Factory Default — +60.0
Changeable During Run — Yes
Minimum — - (Maximum Freq. (F011))
Maximum — + (Maximum Freq. (F011))
Units — Hz
Direct Access Number — F232
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
Direct Access Number — F233
Parameter Type — Numerical
Factory Default — +100.00
Changeable During Run — Yes
Minimum — -250.00
Maximum — +250.00
Units — %
F233
111