TAPs for the SLOT, SHELF, and FAN
Alarm Groups
TAP-103: Clear 'CIO failure'
....................................................................................................................................................................................................................................
Overview
Procedure
....................................................................................................................................................................................................................................
6 - 1 0
This procedure is used to clear the
............................................................................................................................................................
Using the
AID
column from the
1
appropriate shelf associated with the alarm condition.
............................................................................................................................................................
Remove the appropriate shelf cover. All connections can be accessed
2
from the front. For details, refer to
Circuit Pack"
(7-20).
............................................................................................................................................................
Unseat the failed circuit pack without disconnecting any cables. After
3
unseating the pack, remove all connected cables.
............................................................................................................................................................
Insert a replacement circuit pack without seating it (do not push it all
4
the way in).
............................................................................................................................................................
Reconnect all cables to the new circuit pack.
5
............................................................................................................................................................
Reseat the circuit pack.
6
..........................................................................................................................................................
Is
still listed in the CIT
7
CIO failure
IF...
YES
NO
............................................................................................................................................................
Reinstall the shelf cover. For details, refer to
8
Remove/Install Front Cover"
E
S
N D
O F
T E P S
.........................................................................................................................................................................................................................................................
Lucent Technologies - Proprietary
See notice on first page
alarm condition.
CIO failure
NE Alarm List
, identify the
"DLP-608: Remove and/or Install
NE Alarm List
THEN...
Consult the appropriate maintenance
support organization for further
technical assistance.
Continue with
Step
8.
"DLP-607:
(7-17).
Trouble Clearing Tasks
?
365-575-783R1.1
Issue 1, June 2002
Need help?
Do you have a question about the LambdaXtreme and is the answer not in the manual?
Questions and answers