Goodrive3000 series medium voltage VFD
2. The function can be enabled only by disabling input phase loss protection.
Function
Name
code
Overvoltage speed
P11.03
loss protection
Enable the function of overvoltage speed loss protection.
Function
Name
code
Voltage protection of
P11.04
overvoltage stall
Set the protection point of overvoltage stall.
Function
Name
code
P11.05
Current limit action
Automatic current
P11.06
limit level
Frequency
P11.07
decreasing velocity
during current limit
Description
0: Disabled
1: Enabled
Output current
Overvoltage stall
threshold
Output
frequency
Description
120–150% (standard bus voltage)
Description
Ones: current limit:
0:Invalid
1:Valid
Tens: overload alarm of hardware
current limit (for factory
commissioning)
0: Valid
1: Invalid
50.0–200.0% (100% corresponds to
rated current)
0.00–50.00Hz/s
-156-
Goodrive3000 inverter
Setting range
Default
0–1
0
Time t
Time t
Setting range
Default
120–150
130%
Setting range
Default
00–11
01
50.0–200.0
160.0%
0.00–50.00
10.00Hz/s