Goodrive3000 series medium voltage VFD
Function
Name
code
frequency
changing ratio
Action when the
P08.47
frequency setting
is at power off
P08.48
Reserved
P08.49
Reserved
Magnetic flux
P08.50
braking
Input power
P08.51
factor of the VFD
P09 group––PID control
PID reference
P09.00
source
Description
0x000–0x111
LED ones: Action selection when the
digital adjusting frequency is at power
off
0: Save when the power is off
1: Clear when the power is off
LED tens: Action selection when
MODBUS setting frequency is at power
off
0: Save when the power is off
1: Clear when the power is off
LED hundreds: Action selection when
other communication setting frequency
is at power off
0: Save when the power is off
1: Clear when the power is off
0: Invalid
100–150
0.00–1.00
0: Keypad digital setting (P09.01)
1: AI1 setting
2: AI2 setting
3: AI3 setting
4: HDI pulse setting
5: Multi-step speed setting
6: MODBUS communication setting
7: PROFIBUS/CANopen
communication setting
8: Ethernet communication setting
-223-
Goodrive3000 inverter
Setting range
Default
0x000–0x111
0x000
0–150
0
0.00–1.00
0.56
0–9
0
Modify
○
○
○
○
○
○