Goodrive3000 series medium voltage VFD
5.3 Fault information and solution
Fault
Type of fault
code
OC
Input overcurrent
LvI
Input undervoltage
OvI
Input overvoltage
SPI
Input phase loss
PLLF
Phase-locked failed
DC bus
Lv
undervoltage
DC bus
ov
overvoltage
Current detection
ItE
fault
PROFIBUS
E-DP
communication fault
Possible causes
Wrong setting of current loop or
parameters
Hardware circuit abnormal
Rectifiers overload
Input power is abnormal
power-down
Input voltage detection circuit
abnormal
Input power abnormal
Interference
Input voltage detection circuit
abnormal
Input power abnormal
Interference
Input voltage detection circuit
abnormal
The grid environment is abnormal
The circuit of the sample board is
abnormal
Input power abnormal
Interference
Input voltage detection circuit
abnormal
Input power abnormal
Interference
Bus voltage detection circuit
abnormal
The circuit is abnormal or
interfered
Hoare components is broken
PROFIBUS communication offline
Wrong PROFIBUS parameters
setting
-54-
Goodrive3000 PWM rectifier
Countermeasures
Adjust the current loop and
parameters
Ask for service
Adjust the load or rectifier
Check the input power
Ask for service
Check the input power
Check the external interference
Ask for service
Check the input power
Ask for service
Check the external interference
Check and find out the
interference
Ask for service
Check the input power
Ask for service
Check the external interference
Check the input power
Ask for service
Check the external interference
Check and settle the faults
Check communication
Re-set the relevant parameters
Need help?
Do you have a question about the Goodrive3000 Series and is the answer not in the manual?
Questions and answers