Baumer
7.2.3
Integrating the sensor into the PLC project [OXM]
After the GSD file has been installed, the sensor can be used in the PLC project. PLC configur-
ation usually takes place independently of the actual connection in the network. Proceed as fol-
lows:
Instruction:
a) Open the Siemens software.
b) Open the Hardware catalog window.
c) Mark the sensor in the Hardware catalog window, drag and drop it onto the Profinet sub-
system and assign the sensor to the desired Profinet network group.
d) In the Devices and networks window in the tab Properties, you can set the IP address,
the cycle time and other interface options. The combination of slots and modules is already
preset.
e) If necessary, adjust the input address range of the data in the PLC process image and the
name.
f) Compile the project (1) and then load it onto the PLC (2), by clicking the following button:
For more information about the Profinet interface, see
OX200 | V2
1
2
Profinet [OXM]
Operating Manual
Commissioning
[} 22].
|