A H 5 00 M o ti on C on tr ol M od ul e Ma nua l
Example 1: Using the third timer in general mode
1.
H ig h-s peed
t iming
2
.
SM200 and C201
SM204 and C205
SM208 and C209
SM212 and C213
The program is shown below.
Example 2: Using the third timer in cyclic mode
1.
2.
The program is shown below.
3.
3 - 3 2
Users have to select the general mode, and enable the timer, that is, they
have to write K4 into K1SM208.
C208 is enabled. The interval between the rising edge of a pulse received
through X0.2 and the falling edge of the pulse is measured. The interval is
written into C209. (Unit: 0.01 microseconds)
X0.2
t1
X0.0
Users have to write K5 into K1SM208.
C208 is enabled. The interval between the rising edge of a pulse received
through X0.2 and the rising edge of the next pulse is measured. The
interval is written into C209. (Unit: 0.01 microseconds)
X0.2
t1
X0.0
The cyclic mode is used to measure a frequency.
t2
C209
C209
General mode
Unit: 0.01 μs
MOVP
K4
C208
DCNT
t2
C209
C209
Cyclic mode
Unit: 0.01 μs
MOVP
K5
DCNT
C208
t
K1SM208
K10
t
K1SM208
K10