A H 5 00 M o ti on C on tr ol M od ul e Ma nua l
API
Instruction code
112
D
MOVR
Device
X
Y
M
S
D
 S: Source; D: Destination
 The operand S can be a floating-point number.
E xp la nat io n
 When the instruction is executed, the value in S is transferred to D.
 If KnM/KnS is used, it is suggested that M device numbers/S device
 When X0.0 is OFF, the value in (D11, D10) is unchanged. When X0.0 is
E xa mple
Operand
P
S
K
16#
F
Pulse instruction 16-bit instruction 32-bit instruction (6 steps)
When the instruction is not executed, the value in D is unchanged.
numbers should start from a number which is a multiple of 16 in the
decimal numeral system, e.g. K1M0 and K4S16 (decimal numeral
system)
ON, the value F1.2 is transferred to the data register (D11, D10).
X0.0
Transferring a
S, D
floating-point value
KnM KnS
D
W
DMOVR
F1. 2
Function
T
C
V
Z
D10
5 - 7 8