7 Electrical Installation
Wire Gauge and Torque Specifications for UL Listing
Refer to
Three-Phase 600 V Class on page 24
circuit terminals.
Note:
• The recommended wire gauges are based on drive continuous current ratings with 75 °C (167 °F) 600 V class 2 heat-resistant indoor PVC
wire. Assume these conditions:
–Ambient temperature: 40 °C (104 °F) or lower
–Wiring distance: 100 m (328 ft) or shorter
–Normal Duty Rated current value
Three-Phase 600 V Class
Model
Terminals
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5382
-, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5412
-, +1
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
5472
-, +1
+3
*1
For IP20 protection, use wires that are in the range of applicable gauges.

Main Circuit Terminal Block Wiring Procedure

DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before servicing,
disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal capacitor
stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage decreases below 50
Vdc. When all indicators are OFF, remove the covers before measuring for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
The procedures to wire the main circuit terminal block are different for different drive models. Refer to
procedures by drive model.
24
for the recommended wire gauges and tightening torques of the main
Applicable Gauge
Recommended Gauge
(IP20 Applicable
Gauge)
AWG, kcmil
AWG, kcmil
2/0 - 300
4/0 × 2P
(250 - 300)
2/0 - 300
250 × 2P
(250 - 300)
3/0 - 400
350 × 2P
(300 - 400)
3/0 × 2P
1
2/0 - 300
2/0 × 4P
(250 - 300)
2/0 - 300
2/0 × 4P
(250 - 300)
3/0 - 400
4/0 × 4P
(300 - 400)
1/0 × 4P
1
2/0 - 300
3/0 × 4P
(250 - 300)
2/0 - 300
3/0 × 4P
(250 - 300)
3/0 - 400
4/0 × 4P
(300 - 400)
1/0 × 4P
1/0
YASKAWA TOEPC7106170VA GA800 600 V Drive Installation & Primary Operation
Terminal Screw
Size
*1
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
2 - 4/0
M12
Hex self-locking nut
(4/0)
1 - 300
M12
(-)
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
2 - 4/0
M12
Hex self-locking nut
(4/0)
1 - 300
M12
(-)
M12
Hex self-locking nut
M12
Hex self-locking nut
M12
Hex self-locking nut
2 - 4/0
M12
Hex self-locking nut
(4/0)
1 - 300
M12
(-)
Tightening Torque
N∙m (in∙lb)
Shape
35 (310)
35 (310)
35 (310)
35 (310)
Hex bolt (slotted)
32 - 40 (283 - 354)
35 (310)
35 (310)
35 (310)
35 (310)
Hex bolt (slotted)
32 - 40 (283 - 354)
35 (310)
35 (310)
35 (310)
35 (310)
Hex bolt (slotted)
32 - 40 (283 - 354)
Table 7.2