Setpoint Source Segment Setpoints - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

14.3.7

Setpoint source segment setpoints

The four functions "Activate segment setpoint (bit 0)" ... " Activate segment setpoint´(bit 3)"
enable a setpoint change-over to a segment setpoint parameterised for the "sequencer" func-
tion during normal operation.
Preconditions
A setpoint change-over to the respective segment setpoint is only effected if no setpoint
source with a higher priority has been selected.
Details
A segment setpoint is selected in a binary-coded fashion via the triggers assigned to the four
functions "Activate segment setpoint (bit 0)" ... " Activate segment setpoint´(bit 3)" in compli-
ance with the following truth table:
Activate segment setpoint
Bit 3
Bit 2
Bit 1
0x2631:029
0x2631:028
0x2631:027
(P400.29)
(P400.28)
(P400.27)
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
TRUE
FALSE
TRUE
FALSE
FALSE
TRUE
FALSE
FALSE
TRUE
TRUE
FALSE
TRUE
TRUE
TRUE
FALSE
FALSE
TRUE
FALSE
FALSE
...
TRUE
TRUE
TRUE
Parameter
Name / value range / [default setting]
0x2631:026
Function list: Activate segment setpoint (bit 0)
(P400.26)
(Function list: Setp: Segment b0)
• From version 03.00
• For further possible settings, see parameter
0x2631:001
0 Not connected
0x2631:027
Function list: Activate segment setpoint (bit 1)
(P400.27)
(Function list: Setp: Segment b1)
• From version 03.00
• For further possible settings, see parameter
0x2631:001
0 Not connected
4Priority of the setpoint sources
Bit 0
Segment
0x2631:026
(P400.26)
FALSE
TRUE
1
FALSE
2
TRUE
3
FALSE
4
TRUE
5
FALSE
6
TRUE
7
FALSE
8
TRUE
TRUE
(P400.01).
^ 532
(P400.01).
^ 532
Flexible I/O configuration
^ 548
Selection
Frequency setpoint
PID setpoint
No segment setpoint selected
0x4026:001 (P801.01)
0x4026:006 (P801.06)
0x4027:001 (P802.01)
0x4027:006 (P802.06)
0x4028:001 (P803.01)
0x4028:006 (P803.06)
0x4029:001 (P804.01)
0x4029:006 (P804.06)
0x402A:001 (P805.01)
0x402A:006 (P805.06)
0x402B:001 (P806.01)
0x402B:006 (P806.06)
0x402C:001 (P807.01)
0x402C:006 (P807.06)
0x402D:001 (P808.01)
0x402D:006 (P808.06)
Invalid selection
Info
Assignment of a trigger for the "Activate segment setpoint (bit 0)" func-
tion.
Selection bit with the valency 20 for the bit-coded selection and activa-
tion of a parameterised segment setpoint.
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
Notes:
• During normal operation (no active sequence), this function serves to
activate the setpoint of a segment (instead of an entire sequence in
the sequencer operation).
• This function is not intended for the use in the sequencer operation.
Assignment of a trigger for the "Activate segment setpoint (bit 1)" func-
tion.
Selection bit with the valency 2
tion of a parameterised segment setpoint.
Trigger = FALSE: selection bit = "0".
Trigger = TRUE: selection bit = "1".
Notes:
• During normal operation (no active sequence), this function serves to
activate the setpoint of a segment (instead of an entire sequence in
the sequencer operation).
• This function is not intended for the use in the sequencer operation.
Setpoint change-over
Setpoint source segment setpoints
Torque setpoint
0x4026:007 (P801.07)
0x4027:007 (P802.07)
0x4028:007 (P803.07)
0x4029:007 (P804.07)
0x402A:007 (P805.07)
0x402B:007 (P806.07)
0x402C:007 (P807.07)
0x402D:007 (P808.07)
1
for the bit-coded selection and activa-
563

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents