Configuring the network
PROFINET

Basic settings

9.9.2
Basic settings
For communicating with the inverter, the IO controller must be configured.
The configuration of the IO controller comprises
the loading of the device description file into the IO controller,
the assignment of a station name for the inverter and
the assignment of an IP address for the inverter.
The station name and the IP address are assigned by the IO controller. The assignment can
also be made by the Lenze engineering tool.
Preconditions
The entire wiring of the inverter has already been checked for completeness, short circuit
and earth fault.
The GSDML device description file for PROFINET must be downloaded from
http://www.lenze.com/application-knowledge-base/artikel/200804173/0/ . Please
observe the required system requirements an the notes regarding the inverter.
Device description file
The current device description file is installed in the engineering tool used for configuring the
network. Thus, an unambiguous station name is assigned to the inverter which makes it possi-
ble for the IO controller to identify the device in the network and manage the data exchange
with the other network nodes.
The designation of the device description file is as follows:
"GSDML-V<x>.<z>-Lenze-i<NNN>PN<Version>-<yyyy><mm><dd>.xml".
The information in the wildcards (angle brackets) are explained in the following:
Wildcard
Info
x
Major version of the used GSDML scheme
z
Minor version of the used GSDML scheme
NNN
Specifying the inverter designation, e.g. i<550>
Version
First software version that can be used with this GSDML. This data must not be changed.
yyyy
Year of publication
mm
Month of publication
dd
Day of publication
Tab. 2: Explanation of the wildcards in the designation of the device description file
Station name
The station name is required for the clear addressing of the inverter by the IO controller.
The station name of the inverter must be entered into the
with permissible characters according to the PROFINET specification. The characters permissi-
ble for the name allocation are given in the specification.
The station name is read out with
IP address
The IP address makes it possible to access the inverter in the entire network.
For configuring the IP address, the subnet mask and gateway address must also be assigned:
0x2381:001
(P510.01): IP address
0x2381:002
(P510.02): Subnet mask
0x2381:003
(P510.03): Gateway address
All three settings are read out with the parameters
(P511.03).
366
0x2381:004 (P510.04)
0x2382:004
(P511.04).
0x2382:001 (P511.01)
parameter
...
0x2382:003