9.6.3
Station address setting
Each network node must be provided with a unique station address.
The parameters for addressing the device are described below.
Details
The station address of the inverter can be optionally set via the DIP switches on the device
•
labelled with "1" ... "64" or in
The setting that is active when the inverter is switched on is the effective setting.
•
The labelling of the DIP switches corresponds to the values of the individual DIP switches
•
for determining the station address (see the following example).
The active station address is shown in
•
View of the DIP switch
Example of how the station address is set via the DIP switches
DIP switch
Setting
Value
Station address
= sum of all values = 16 + 4 + 2 + 1 = 23
Parameter
Name / value range / [default setting]
0x2341:001
PROFIBUS settings: Station address
(P510.01)
(PROFIBUS sett.: Station address)
1 ... [3] ... 125
0x2342:001
Active PROFIBUS settings: Active station address
(P511.01)
(PROFIBUS diag.: Act.station addr)
• Read only
0x2343
PROFIBUS switch position
(P509.00)
(PROFIBUS switch)
• Read only
0x2341:001
(P510.01). (The DIP switches have priority.)
0x2342:001
(P511.01).
64
32 16
PROFIBUS
Address
64
32
16
OFF
OFF
ON
0
0
16
Configuring the network
8
4
2
1
O
N
8
4
OFF
ON
0
4
Info
Optional setting of the station address (instead of setting via DIP
switches 1 ... 64).
• The station address set here only becomes effective if DIP switches
1 ... 64 have been set to OFF before mains switching.
• A change in the station address only becomes effective after a restart
of PROFIBUS communication.
Display of the active station address.
Display of the DIP switch setting at the last mains power-on.
• The displayed value corresponds to the sum of the individual DIP
switch values 1 ... 64.
PROFIBUS
Station address setting
2
1
ON
ON
2
1