9.6.3

Station address setting

Each network node must be provided with a unique station address.
The parameters for addressing the device are described below.
Details
The station address of the inverter can be optionally set via the DIP switches on the device
labelled with "1" ... "64" or in
The setting that is active when the inverter is switched on is the effective setting.
The labelling of the DIP switches corresponds to the values of the individual DIP switches
for determining the station address (see the following example).
The active station address is shown in
View of the DIP switch
Example of how the station address is set via the DIP switches
DIP switch
Setting
Value
Station address
= sum of all values = 16 + 4 + 2 + 1 = 23
Parameter
Name / value range / [default setting]
0x2341:001
PROFIBUS settings: Station address
(P510.01)
(PROFIBUS sett.: Station address)
1 ... [3] ... 125
0x2342:001
Active PROFIBUS settings: Active station address
(P511.01)
(PROFIBUS diag.: Act.station addr)
• Read only
0x2343
PROFIBUS switch position
(P509.00)
(PROFIBUS switch)
• Read only
0x2341:001
(P510.01). (The DIP switches have priority.)
0x2342:001
(P511.01).
64
32 16
PROFIBUS
Address
64
32
16
OFF
OFF
ON
0
0
16
Configuring the network
8
4
2
1
O
N
8
4
OFF
ON
0
4
Info
Optional setting of the station address (instead of setting via DIP
switches 1 ... 64).
• The station address set here only becomes effective if DIP switches
1 ... 64 have been set to OFF before mains switching.
• A change in the station address only becomes effective after a restart
of PROFIBUS communication.
Display of the active station address.
Display of the DIP switch setting at the last mains power-on.
• The displayed value corresponds to the sum of the individual DIP
switch values 1 ... 64.
PROFIBUS
Station address setting
2
1
ON
ON
2
1
295