Networks; Canopen - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Electrical installation

Networks

CANopen

4.4
Networks
4.4.1
CANopen
Typical topologies
A1
120
R
X216
CH
CL
CG
Terminal description
Connection
Connection type
Min. cable cross-section
Min. cable cross-section
Max. cable cross-section
Max. cable cross-section
Stripping length
Stripping length
Tightening torque
Tightening torque
Required tool
Basic network settings
Use the DIP switch to set the node address and baud rate and to activate the integrated bus
terminating resistor.
Bus termination
R
OFF
Inactive
ON
Active
Bold print = default setting
The network must be terminated with a 120 Ω resistor at the physically first and
last node.
Set the "R" switch to ON at these nodes.
64
A2
120
R
X216
CH
CL
CG
mm²
AWG
mm²
AWG
mm
inch
Nm
lb-in
R
d
c
b
a
Baud
Baud rate
d
c
b
a
OFF
ON
OFF
ON 20 kbps
OFF
OFF
ON
ON 50 kbps
OFF
OFF
ON
OFF 125 kbps
OFF
OFF
OFF
ON 250 kbps
OFF
OFF
OFF
OFF Value from parameter (500 kbps)
OFF
ON
OFF
OFF 1 Mbps
All other combinations
Value from parameter (500 kbps)
Line
A3
120
R
X216
CH
CL
CG
CANopen
X216
pluggable spring terminal
0.5
22
2.5
12
10
0.39
-
-
0.4 x 2.5
64 32 16 8
4
2
1
O
N
CAN Address
An
120
R
X216
CH
CL
CG
CAN node address
64
32
16
8
4
2
OFF OFF OFF OFF OFF OFF OFF
Value from parameter
Node address - example:
OFF OFF ON OFF ON ON ON
Node address = 16 + 4 + 2 + 1 = 23
1