9.5.8

Data mapping

The process of data mapping is used for defining which Modbus registers read or write to
which inverter parameters.
Details
There are fixedly defined Modbus registers for common control and status words, which
are located in consecutive blocks, in order to facilitate communication with OPC servers
and other Modbus masters. In order to access all relevant data of the inverter, only a mini-
mum number of commands is required.
In addition, 24 registers are provided for variable mapping, i. e. free assignment to inverter
parameters.
Predefined Modbus control registers
These registers are provided with write and read access.
The cross-reference in column 2 leads to the detailed parameter description.
Modbus registers
42101
42102
42103
42104
42105
42106
42107
42108
42109 ... 42121
Predefined Modbus status registers
These registers are only provided with read access.
The cross-reference in column 2 leads to the detailed parameter description.
Modbus registers
42001
42002
42003
42004
42005
42006
42007
42008
42009
42010
42011
42012
42013
42014 ... 42021
Permanently assigned parameter
Address
0x400B:001 (P592.01)
0x400B:005 (P592.05)
0x4008:002 (P590.02)
0x4008:003 (P590.03)
0x400B:007 (P592.07)
0x6071
0x4008:001 (P590.01)
0x4008:004 (P590.04)
-
Permanently assigned parameter
Address
0x400C:001 (P593.01)
0x400C:006 (P593.06)
0x603F (P150.00)
0x400C:005 (P593.05)
0x2D89 (P106.00)
0x2D88 (P104.00)
0x6078 (P103.00)
0x2DA2:002 (P108.02)
0x2D84:001 (P117.01)
0x2D87 (P105.00)
0x60FD (P118.00)
0x6077 (P107.00)
-
Configuring the network
Name
AC Drive control word
Network setpoint frequency (0.01)
NetWordIN2
NetWordIN3
PID setpoint
Target torque
NetWordIN1
NetWordIN4
Reserved
Name
AC Drive status word
Frequency (0.01)
Error code
Drive status
Motor voltage
Motor current
Current actual value
Apparent power
(42008 = High Word, 42009 = Low Word)
Heatsink temperature
DC-bus voltage
Digital inputs (only bit 16 ... bit 31)
Torque actual value
Reserved
Modbus RTU
Data mapping