Configuring the network
EtherNet/IP

Short setup

9.7.9
Short setup
Typically, an EtherNet/IP network consists of segments that contain point-to-point connec-
tions in a star configuration (see "Typical topologies" in the section
In the following, the required steps are described to control the device as EtherNet/IP adapter.
Conditions for commissioning
The control unit (CU) of the inverter is provided with EtherNet/IP (from firmware 02.01).
The device is networked as EtherNet/IPAdapter with an EtherNet/IP Scanner and, if neces-
sary, further EtherNet/IP nodes, see "Typical topologies" in the section
An Engineering PC with the programming software »RSLogix™ 5000« (from version 20) is
connected to the Scanner.
Current device description files for EtherNet/IP are available.
EDS files for Lenze devices: Download
The files are installed via the "EDS Hardware Installation Tool" of the »RSLogix™ 5000«.
Allen-Bradley control systems do not need any EDS files to add devices to their configu-
ration.
An »RSLogix™ 5000« project has been created and is in the offline state.
The CPU and Ethernet adapter of the PLC (Scanner) have been configured.
All EtherNet/IP nodes are supplied with voltage and are switched on.
How to configure the network:
1. Configure IP communication.
1. Make IP basic settings at the Engineering PC.
The PC with the programming tool »RSLogix™ 5000« must be in the same network as
the devices to be configured.
2. Set IP address of the inverter (adapter) via rotary encoder switch and parameter
0x23A1:001
(P510.01).
3. Set subnet mask:
0x23A1:002 (P510.02)
4. Set gateway address:
4Basic settings
^ 317
The configuration of the IP communication is now completed.
2. Activate network control in the inverter.
1. Activate network control:
2. Set network as standard setpoint source:
If a different standard setpoint source is set and the network control is activated, a
change-over to the network setpoint is possible via the AC Drive control word
001
(P592.01).
4Restart communication
4General network settings
The network control is now activated.
3. Save parameter settings:
3. Execute I/O configuration with »RSLogix™ 5000« (version 20).
1. Start the »RSLogix™ 5000«.
2. Open or recreate a »RSLogix™« project.
3. Configure the cyclic data transfer (Implicit Messaging).
4Process data transfer
4Customer specific configurations
4. Configure the acyclic data transfer (Explicit Messaging).
4Parameter data transfer
The I/O configuration is now completed.
The configuration of the network is now completed.
346
0x23A1:003 (P510.03)
0x2631:037 (P400.37)
= "Network control active [114]"
0x2860:001 (P201.01)
^ 331
^ 332
0x2022:003 (P700.03)
= "On / start [1]"
^ 332
^ 337
^ 342
).
4EtherNet/IP
^ 68
.
4EtherNet/IP
^ 68
= "Network [5]"