Example 1: Start/stop (1 signal) and reversal

This example shows a simple control option via two switches which should be sufficient for
many applications:
Switch S1 starts the motor in forward direction of rotation. Switch S1 in the initial position
stops the motor again.
Switch S2 switches the direction of rotation.
Connection plan
X3
0 ... 10 V
R1
The example uses the preset I/O configuration of the inverter:
Parameter
0x2631:001 (P400.01)
0x2631:002 (P400.02)
0x2631:013 (P400.13)
Input signals
Frequency setpoint selection
Trigger
Function
Constant TRUE [1]
Enable inverter
Digital input 1 [11]
Run
Digital input 3 [13]
Invert rotation
Output signals
Output frequency
0x2DDD
Status signals
Running [50]
Stop active [53]
Rotational direction reversed [69]
The status signals can be assigned to digital outputs.
If the inverter is enabled and no error is active, the motor can be started with the "Run" function in forward rotating direction.
If "Run" is set to FALSE, the motor is stopped with the stop method set in
S1
S2
Name
Enable inverter
Run
Reverse rotational direction
60 Hz
50 Hz
40 Hz
30 Hz
20 Hz
10 Hz
0 Hz
60 Hz
50 Hz
40 Hz
30 Hz
20 Hz
10 Hz
0 Hz
-10 Hz
-20 Hz
-30 Hz
-40 Hz
-50 Hz
-60 Hz
4Configuration of digital outputs
Flexible I/O configuration
Example 1: Start/stop (1 signal) and reversal
function
Potentiometer R1 Frequency setpoint selection
Switch S1 Run
Switch S2 Reverse rotational direction
Setting for this example (corresponds to
default setting)
Constant TRUE [1]
Digital input 1 [11]
Digital input 3 [13]
^ 603
0x2838:003
(P203.03). In the example: Stop with standard ramp.
Start / stop motor
t
t
t
t
t
t
t
t
537