9.6.13

Error codes for parameter data transfer

The following table lists all possible error codes for the acyclic data exchange:
Error code
Description
0x0000
Parameter number impermissible
0x0001
Parameter value cannot be changed
0x0002
Lower or upper value limit exceeded
0x0003
Subindex impermissible
0x0004
No array
0x0005
Incorrect data type
0x0006
No setting permitted (only resettable)
0x0007
Description element cannot be changed
0x0008
Reserved
0x0009
Description data not available
0x000A
Reserved
0x000B
No parameter change rights
0x000C
Reserved
0x000D
Reserved
0x000E
Reserved
0x000F
No text array available
0x0010
Reserved
0x0011
Request cannot be executed due to the operating
state
0x0012
Reserved
0x0013
Reserved
0x0014
Value impermissible
0x0015
Response too long
0x0016
Parameter address impermissible
0x0017
Format impermissible
0x0018
Number of values not consistent
0x0019
Axis impermissible
0x001A
Reserved
...
0x00FF
Configuring the network
Error codes for parameter data transfer
Explanation
Access to non-available parameter.
Change access to a parameter value that cannot be
changed.
Change access with value beyond the value limits.
Access to non-available subindex.
Access with subindex to non-indicated parameter.
Change access with value that does not match the
data type of the parameter.
Change access with a non-zero value where it is not
permitted.
Change access to a description element that cannot
be changed.
(PROFIdrive profile V2: PPO-Write requested in IR is
not available.)
Access to non-available description (parameter value
is available).
(PROFIdrive profile V2: Wrong access group.)
Change access with missing parameter change rights. -
(PROFIdrive profile V2: Wrong password.)
(PROFIdrive profile V2: Text cannot be read in cyclic
data transfer.)
(PROFIdrive profile V2: Name cannot be read in cyclic
data transfer.)
Access to non-available text array (parameter value is
available).
(PROFIdrive profile V2: No PPO-Write.)
Access is not possible for temporary reasons that are
not specified in detail.
(PROFIdrive profile V2: Other error.)
(PROFIdrive profile V2: Date cannot be read in cyclic
data transfer.)
Change access with the value that is within the value
limits but that is impermissible for other permanent
reasons (parameters with defined individual values).
The length of the current response exceeds the maxi-
mum length transferrable.
Impermissible value or value which is not supported
for the attribute, number of subindexes, parameter
number, or subindex, or a combination.
Write request: Impermissible or non-supported for-
mat of parameter data.
Write request: Number of parameter data values does
not match the number of subindexes in the parameter
address.
Access to non-available axis. For double axis, only
0x00 or 0x01 permitted.
-
PROFIBUS
Additional infor-
mation
-
Subindex
Subindex
Subindex
-
-
Subindex
Subindex
-
-
-
-
-
-
-
-
-
-
-
Subindex
-
-
-
-
-
-
311