Selection Of Setpoint Source - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Basic setting

Selection of setpoint source

7.4
Selection of setpoint source
The selected "setpoint source" serves to provide the inverter with its setpoint. The setpoint
source can be selected individually for each operating mode.
Possible setpoint sources are:
Analog inputs
Keypad
Network
Parameterisable setpoints (presets)
Digital inputs (configured as HTL input for pulse train or HTL encoder)
"Motor potentiometer" function
"Sequencer" function
Details
For applications only requiring one setpoint it is sufficient to define the standard setpoint
source in the following parameters.
For applications requiring a change-over of the setpoint source during operation, the func-
tions for setpoint change-over have to be configured accordingly.
^ 546
Parameter
Name / value range / [default setting]
0x2860:001
Frequency control: Default setpoint source
(P201.01)
(Stnd. setpoints: Freq. setp. src.)
1 Keypad
2 Analog input 1
3 Analog input 2
4 HTL input
5 Network
11 Frequency preset 1
12 Frequency preset 2
13 Frequency preset 3
14 Frequency preset 4
15 Frequency preset 5
16 Frequency preset 6
17 Frequency preset 7
18 Frequency preset 8
19 Frequency preset 9
20 Frequency preset 10
21 Frequency preset 11
22 Frequency preset 12
23 Frequency preset 13
24 Frequency preset 14
25 Frequency preset 15
148
(from version 04.00)
4Setpoint change-over
Info
Selection of the standard setpoint source for operating mode "MS:
Velocity mode".
• The selected standard setpoint source is always active in the operat-
ing mode
0x6060 (P301.00)
= "MS: Velocity mode [-2]" when no set-
point change-over to another setpoint source via corresponding trig-
gers/functions is active.
4Setpoint change-over
^ 546
The setpoint is specified locally by the keypad.
• Default setting:
0x2601:001 (P202.01)
• Use the
and
navigation keys to change the keypad setpoint
(also during running operation).
The setpoint is defined as analog signal via the analog input 1.
4Analog input 1
^ 597
The setpoint is defined as analog signal via the analog input 2.
4Analog input 2
^ 601
The digital inputs DI3 and DI4 can be configured as HTL input to use an
HTL encoder as setpoint encoder or define the setpoint as a reference
frequency ("pulse train").
4HTL input setpoint source
^ 565
The setpoint is defined as process data object via the network.
4Configuring the network
^ 226
For the setpoint selection, preset values can be parameterised and selec-
ted.
4Setpoint source of preset setpoints
^ 554

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents