Diagnostics and fault elimination
Diagnostics parameter
Diagnostics of the inputs and outputs
Parameter
Name / value range / [default setting]
0x4016:005
Digital output 1: Terminal state
• Read only
0 FALSE
1 TRUE
0x4016:006
Digital output 1: Trigger signal state
• Read only
0 FALSE
1 TRUE
0x4017:005
Digital output 2: Terminal state
• Read only
• Only available for application I/O.
0 FALSE
1 TRUE
0x4017:006
Digital output 2: Trigger signal state
• Read only
• Only available for application I/O.
0 FALSE
1 TRUE
0x4018:005
Relay: Relay state
• Read only
0 FALSE
1 TRUE
0x4018:006
Relay: Trigger signal state
• Read only
0 FALSE
1 TRUE
Related topics
4Configuration of digital inputs
4Configuration of digital outputs
6.2.5.2

Analog inputs and outputs

The following parameters serve to diagnose the analog inputs and outputs of the inverter.
Parameter
Name / value range / [default setting]
0x2DA4:001
Diagnostics of analog input 1: Value in percent
(P110.01)
(AI1 diagnostics: AI1 terminal %)
• Read only: x.x %
0x2DA4:002
Diagnostics of analog input 1: Frequency value
(P110.02)
(AI1 diagnostics: AI1 scaled freq.)
• Read only: x.x Hz
0x2DA4:003
Diagnostics of analog input 1: Process controller value
(P110.03)
(AI1 diagnostics: AI1 scaled PID)
• Read only: x.xx PID unit
0x2DA4:004
Diagnostics of analog input 1: Torque value
(P110.04)
(AI1 diagnostics: AI1 scaled torq.)
• Read only: x.x %
130
^ 594
^ 603
Info
Display of the logic state of output terminal X3/DO1.
Display of the logic state of the trigger signal for digital output 1 (without
taking a ON/OFF delay set and inversion into consideration).
Display of the logic state of output terminal X3/DO2.
Display of the logic state of the trigger signal for digital output 2 (without
taking a ON/OFF delay set and inversion into consideration).
Display of the logic state of the relay.
Display of the logic state of the trigger signal for the relay (without tak-
ing a ON/OFF delay set and inversion into consideration).
Info
Display of the current input value at X3/AI1 scaled as value in percent.
• 100 % ≡ 10 V or 20 mA or 5 V
Display of the current input value at X3/AI1 scaled as a frequency value.
• The standard setpoint source for operating mode
"MS: Velocity mode [-2]" is selected in
Display of the current input value at X3/AI1 scaled as a process controller
value.
• The standard setpoint source for the reference value of PID control is
selected in
0x2860:002
(P201.02).
Display of the current input value at X3/AI1 scaled as a percentage tor-
que value.
• 100 % ≡ permissible maximum torque
• The standard setpoint source for operating mode
"MS: Torque mode [-1]" is selected in
0x6060 (P301.00)
=
0x2860:001
(P201.01).
0x6072 (P326.00)
0x6060 (P301.00)
=
0x2860:003
(P201.03).