Flexible I/O configuration
Setpoint change-over

Priority of the setpoint sources

14.3.1
Priority of the setpoint sources
Since only one setpoint source can be active at a time, the following priorities apply:
Flexible I/O configuration or keypad control active
0x2631:037 (P400.37)
Prio 1: Functions for setpoint change-over
The priority of the functions results from the assigned triggers (in the
order of the selection list):
1. Constant TRUE [1]
2. Digital input 1 [11]
3. Digital input 2 [12]
4. Digital input 3 [13]
5. ...
Prio 2: Set standard setpoint source
0x2860:001
(P201.01): Frequency control: Default setpoint source
0x2860:002
(P201.02): PID control: Default setpoint source
4Selection of setpoint source
^ 148
Example of allocating priority
Parameter
0x2631:014 (P400.14)
0x2631:016 (P400.16)
Digital input 4
Digital input 5
FALSE
FALSE
TRUE
TRUE
14.3.2

Analog input setpoint source

The following functions are used to select analog input 1 or analog input 2 as setpoint source.
Preconditions
A setpoint change-over to the respective analog input is only effected if no setpoint source
with a higher priority has been selected.
Parameter
Name / value range / [default setting]
0x2631:014
Function list: Activate AI1 setpoint
(P400.14)
(Function list: Setp: AI1)
• For further possible settings, see parameter
0x2631:001
0 Not connected
548
= FALSE
Name
Activate AI1 setpoint
Activate keypad setpoint
Active setpoint source
FALSE
Standard setpoint source set in
TRUE
Analog input 1
FALSE
keypad
TRUE
Keypad (since "Digital input 4" trigger is higher in the selection list than "Digital input 5" trigger)
4Priority of the setpoint sources
(P400.01).
^ 532
Network control active
0x2631:017 (P400.17)
0x2631:037 (P400.37)
Prio 1: Setpoint source selected via network control word
4General network settings
^ 227
Prio 2: Set standard setpoint source
0x2860:001
(P201.01): Frequency control: Default setpoint source
0x2860:002
(P201.02): PID control: Default setpoint source
4Selection of setpoint source
^ 148
Setting for this example
Digital input 5 [15]
Digital input 4 [14]
0x2860:001 (P201.01)
^ 548
Info
Assignment of a trigger for the "Activate AI1 setpoint" function.
Trigger = TRUE: analog input 1 is used as setpoint source (if the trigger
assigned has the highest setpoint priority).
Trigger = FALSE: no action / deactivate function again.
4Analog input 1
^ 597
= FALSE
= TRUE