Keypad; Keypad Language Selection; Keypad Setpoint Increment; Keypad Scaling Of Speed Display - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Additional functions

Keypad

Keypad status display

11.2
Keypad
For the keypad various settings can be made, which are described in detail in the following
subchapters.
11.2.1

Keypad language selection

Parameter
Name / value range / [default setting]
0x2863
Keypad language selection
(P705.00)
(KP language)
0 No language selected
1 English
2 German
11.2.2

Keypad setpoint increment

Parameter
Name / value range / [default setting]
0x2862
Keypad setpoint increment
(P701.00)
(KP setp. incr.)
1 ... [1] ... 100
11.2.3

Keypad scaling of speed display

Parameter
Name / value range / [default setting]
0x4002
Speed display scaling
(P702.00)
(Scal.speed fact.)
0.00 ... [0.00] ... 650.00
0x400D
Scaled actual value
(P101.00)
(Scaled act value)
• Read only: x Units
11.2.4
Keypad status display
During operation, the keypad displays the output frequency of the inverter, or with an active
PID control it shows the process controller setpoint. Alternatively, an optional diagnostic
parameter can be displayed during operation.
Parameter
Name / value range / [default setting]
0x2864
Keypad status display
(P703.00)
(KP status displ.)
0x00000000 ... [0x00000000] ... 0xFFFFFF00
422
Info
Language selection for the keypad display.
Info
Adaptation of the increment for keypad setpoints when a keypad arrow
key is pressed once. The value set serves as a multiplier for the preset
increments.
Preset increments:
• 0.1 Hz for frequency setpoint
0x2601:001
• 0.01 PUnit for process controller setpoint
• 1 % for torque setpoint
0x2601:003
Notes:
• With a setting > 1, the option of repeatedly changing the setpoint by
pressing the key for a longer time is deactivated.
• The setting only has an impact on the keypad setpoints.
Example: with the setting "5", the keypad frequency setpoint is
increased/decreased by 0.5 Hz every time the key is pressed.
Info
Factor for the scaling of the speed display in
• With the setting "0.00", no scaling takes place.
• Example: with the "16.50" and the actual frequency = 50 Hz,
(P101.00)
shows the speed "825 rpm".
Display of the current speed in application units.
Info
0 = normal display depending on the operating mode
• In case of an active frequency control, the keypad displays the output
frequency of the inverter.
• In case of active PID control, the keypad displays the current Process
controller setpoint in [P-Unit].
As an alternative, an optional diagnostic parameter can be set here,
which is to be shown on the keypad during operation.
• Format: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
• The lowest byte is always 0x00.
• The keypad can be used to select the desired diagnostics parameter
from a list.
(P202.01).
0x2601:002
(P202.02).
(P202.03).
0x400D
(P101.00).
0x400D