Example 2: Change-Over From Terminal Control To Network Control - Lenze i55AE125B Manual

Cabinet 0.25 ... 90 kw
Table of Contents

Advertisement

Flexible I/O configuration
Control source change-over

Example 2: Change-over from terminal control to network control

14.1.2
Example 2: Change-over from terminal control to network control
The control is executed primarily via the I/O terminals: Switch S1 serves to start and stop
the motor.
Switch S2 serves to activate the network control. In case of activated keypad control, the
motor can only be started via the network control word. However, the condition is that
switch S1 is closed.
If switch S1 is opened again, the motor is stopped (irrespective of the active control
source).
Connection plan
X3
0 ... 10 V
R1
Parameter
0x2631:001 (P400.01)
0x2631:002 (P400.02)
0x2631:004 (P400.04)
0x2631:037 (P400.37)
0x2824 (P200.00)
Input signals
Frequency setpoint selection
Trigger
Function
Constant TRUE [1]
Enable inverter
Digital input 1 [11]
Run
Digital input 2 [12]
Activate network control
Network control word: Run forward
Output signals
Output frequency
0x2DDD
Status signals
Running [50]
Stop active [53]
Local control active [104]
Remote control active [105]
The status signals can be assigned to digital outputs.
When changing over to another control source, the motor is first stopped with the stop method set in
The motor will also be stopped if the "Run" function is deactivated (irrespective of the active control source).
Commands via network are ignored if the network control is not active.
530
S1 S2
Name
Enable inverter
Run
Reset fault
Activate network control
Control selection
60 Hz
50 Hz
40 Hz
30 Hz
20 Hz
10 Hz
0 Hz
60 Hz
50 Hz
40 Hz
30 Hz
20 Hz
10 Hz
0 Hz
-10 Hz
-20 Hz
-30 Hz
-40 Hz
-50 Hz
-60 Hz
4Configuration of digital outputs
function
Potentiometer R1 Frequency setpoint selection
Switch S1 Run
Switch S2 Activate network control
Setting for this example
Constant TRUE [1]
Digital input 1 [11]
Not connected [0]
Digital input 2 [12]
Flexible I/O configuration [0]
^ 603
0x2838:003
(P203.03).